Housed in a freestanding cabinet, GLX series inverter is designed to work rugged for even the most demanding application.
| Capacity: | 1-18 KW/KVA |
| Input: | 120V, 208 or 277V, single phase |
| Output: | 120V, 208 or 277V |
| Charging: | Per UL 924 utilizing multi-stage charger to prolong battery life |
| Labels: | Listed to UL924. Compliant with NFPA 101 and NEC |
| Construction: | Cold-rolled steel finished with electrostatic powder coat paint to prevent corrosion. |
| Warranty: |
|
| Runtime: | 90 minutes minimum on standard configuration. Consult factory for other runtime. |
| Battery type: | VRLA |
| Battery protection: | LVD – low voltage discharge to prevent excessive discharge. |
| Circuit protection: | Input breakers on AC and DC provided |
| Cooling: | active ventilation and temperature sensing to control integral fans |
| Temperature rating: | 0 – 40 °C (32 – 104 °F) |